GGD AC LV Switch Panel


 

GGD AC LV Switchgear satisfies the requirements of standards of GB7251.1, JB/T5877 and IEC439-1, and is adapted to the power system of 380-660V, 3-phase AC 50-60Hz, used for no-load compensation and distribution and electromotor controlling, indoor use.

 

◆ The ambient temperature should be not higher than +40℃, not lower than -5℃. The average temperature during 24 hours should be not higher than +35℃;
◆ Latitude should not be over 2000m;
◆ The relative humidity of ambient air should be not more than 50% when the highest temperature is +40℃. The relative high humidity is allowed in lower temperature. (For example, 90% when +20℃);
◆ Gradient between the equipment and vertical side should be no higher than 5°during installation;
◆ Cabinet should be installed at sites with no fierce shaking and impacts, and at places to avoid electric component from erodent.
◆ Users may negotiate with the manufacturer when special requirements.

 

4.1 Basic technical parameter

Main Loop Rated Voltage (V)
AC 380, 660
Auxiliary Loop Rated Voltage (V)
AC 220, 380; DC 110, 220
Rated frequency (Hz)
50(60)
Rated Insulated Voltage (V)
660(1000)
Rated Current (A)
≤3150
Short Time Withstanding Current (kA/Is)
15, 30, 50
Peak Value Withstanding Current (kA/O. Is)
30, 63, 105
Frequency Withstand Voltage (V/min)
Main Loop
2500
Branch Loop
1760
Bus Bar
A, B, C, N
Protection Degree
IP30

 
4.2 Main loop design
There are 129 designs to main loop of GGD cabinet, with total 298 specifications. ( Not include schemes and specs derived by functional changes of auxiliary loop and change of controlling voltage.)
 